THIẾT BỊ PHÂN TÍCH CHẤT LƯỢNG ĐIỆN NĂNG PQ3198

• Verify power problems in accordance with the IEC61000-4-30 Class A standard

• High accuracy and continuous gapless recording (V: ±0.1% of nominal voltage, A: ±0.1% rdg. ±0.1% f.s., W: ±0.2% rdg. ±0.1% f.s.)

• Broadband voltage range lets you measure even high-order harmonic components of up to 80 kHz

• Maximum 6000 V peak transient voltage up to 700 kHz

• Measure up to 6000 A AC

• Two systems of power measurement and efficiency calculation for (ch 1, ch 2, ch 3) and ch 4

• Make simple measurements of inverters with 40 to 70 Hz fundamental frequency and max. 20 kHz carrier frequency

• Easily create reports with bundled PQ ONE application software

• Optional GPS BOX for synchronizing multiple devices

Hioki portable power meters and analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The new and improved PQ3198 is a power quality analyzer for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues. New features include the ability to drive current sensors straight from the PQA and enhanced recording capabilities.

 Record quality data for power systems

Maintain and manage power supplies and analyze problems more easily and reliably than ever before

 

 Analyze equipment power problems

Analyze equipment power problems

 

 Record quality data for power systems

Record quality data for power systems

 

 Measure AC DC power

Measure AC/DC power

 

 Capture power anomalies reliably with simple settings

Capture power anomalies reliably with simple settings

 

 Simultaneously record event waveforms and trend graphs

Simultaneously record event waveforms and trend graphs

 

 Simultaneously record event waveforms and trend graphs_2

Simultaneously record event waveforms and trend graphs

 

 International standard IEC 61000-4-30 Ed. 2 Class A compliant

International standard IEC 61000-4-30 Ed. 2 Class A compliant

 High-voltage, wideband performance

High-voltage, wideband performance

 Two-circuit measurement

Two-circuit measurement

 Verify the quality of power supplied by an EV rapid charger

Verify the quality of power supplied by an EV rapid charger

 Simple inverter measurement

Simple inverter measurement

 No need for an external power supply

No need for an external power supply

 400 Hz line measurement

400 Hz line measurement

 Wide array of ranges to accommodate all applications

Wide array of ranges to accommodate all applications

 Easy-to-understand display of parameters

Easy-to-understand display of parameters

 Automatic sensor detection to avoid erroneous measurement

Automatic sensor detection to avoid erroneous measurement

 Simple setup functionality for simplified configuration of recording parameters

Simple setup functionality for simplified configuration of recording parameters

 GPS time synchronization

GPS time synchronization

 Analyze data and generate reports with HIOKI’s PQ ONE power quality analysis software

Analyze data and generate reports with HIOKI’s PQ ONE power quality analysis software

 Event list PQ ONE

Event list < PQ ONE >

 Event statistics PQ ONE

Event statistics < PQ ONE >

 EN 50160 judgment function PQ ONE

EN 50160 judgment function < PQ ONE >

 PC Application Program GENNECT Cross for Windows

PC Application Program < GENNECT Cross for Windows >

 

 

Chia SẻShare on FacebookPrint this pageShare on Google+Share on LinkedIn
Measurement line type Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel for voltage, current, power measurement (AC or DC measurement)
Voltage ranges Voltage measurement: 600.00 V rms
Transient measurement 6.0000 kV peak
Current ranges 500.00 mA to 5.0000 kA AC (depends on current sensor in use)
Power ranges 300.00 W to 3.0000 MW (determined automatically based on voltage and current range in use)
Basic accuracy Voltage: ±0.1% of nominal voltage
Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy
Active power: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Measurement items 1. Transient voltage : 2 MHz sampling
2. Frequency cycle : Calculated as one cycle, 40 to 70 Hz
3. Voltage (1/2) RMS: one cycle calculation refreshed every half cycle
Current (1/2) RMS: half-cycle calculation
4. Voltage swell, Voltage dips, Voltage interruption
5. Inrush current
6. Voltage waveform comparison
7. Instantaneous flicker value: As per IEC61000-4-15
8. 200 ms frequency: Calculated as 10 or 12 cycles,40 to 70 Hz
9. 10 sec frequency: Calculated as the whole-cycle time during the specified 10 s period, 40 to 70 Hz
10. Voltage waveform peak, Current waveform peak
11. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor, and efficiency
12. High-order harmonic component (voltage/ current): 2 kHz to 80 kHz
13. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50 th orders
14. Harmonic voltage-current phase angle: 1th to 50 th orders
15. Total harmonic distortion factor (voltage/ current)
16. Inter harmonic (voltage/ current): 0.5 th to 49.5 th order
17. K Factor (multiplication factor)
18. IEC Flicker, Δ V10 Flicker
Record Repeated ON: 1 year, Maximum recording event: 9999 × 366 days (up to 9999 events per day)
Repeated off: 35 days, maximum recording event: 9999 events
Interfaces SD/SDHC memory card, LAN (HTTP server function / FTP function), USB2.0 (for communication)
Display 6.5-inch TFT color LCD (640 × 480 dots)
Power supply AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery Pack Z1003 (Continuous use: 180 minutes, Charging time: Max. 5 hr 30 m with AC adapter)
Dimensions and mass 300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.6 kg (91.7 oz) (including Battery Pack Z1003)
Accessories Instruction manual ×1, Measurement guide ×1, Voltage Cord L1000 ×1 set (Red/ Yellow/ Blue/ Gray each 1, Black 4, 3m (9.84ft) length, Alligator clip ×8), Color clip, AC Adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, SD Memory Card 2GB Z4001 ×1, Application software (PQ ONE) ×1
file docs ( 0 bytes ) down load